Display
- Dual-line LCD with backlight
- Both lines 14-segment alphanumeric
- Top: 0.7” / 17.8 mm
- Bottom: 0.4” / 10.2 mm
- Display may be programmed to turn red and flash a user-defined message on alarm condition
Operating Temperature Range
- -40° to 75° C for Safe Area Product
- -40° to 70° C for Hazardous Area Products
Storage Temperature Range
Connections
- Removable screw terminals accept 12 to 22 AWG
Weight
- 8.7 oz. - 247 g with option board
Accuracy
- ± 0.02 % of span ± 1 count
- Square root and programmable exponent: 10-100 % Full Scale
Hazardous Area Approvals
- ATEX: II 1G, Ex ia IIC T4 Ga, Ta = -40° C to +70° C Certificate Number: CML 17ATEX2015X
- IECEx: Ex ia IIC T4 Ga, Tamb = -40° C to +70° C Certificate Number: IECEx CML 17.0008X
- UL & C-UL Listed as Intrinsically Safe and Nonincendive: Class I, Div. 1, Groups A, B, C and D T4, Class I, Div. 2, Groups A, B, C and D T4 Ex ia IIC T4 (Canada), Class I Zone 0, Zone 1 AEx ia IIC T4 (U.S.) Class I Zone 2, Group IIC T4 (U.S.) PROCESS CONTROL EQUIPMENT FOR USE IN HAZARDOUS LOCATIONS
- UL & C-UL 61010 Listed for Electrical Safety and Type 4X Environmental: Standards for Safety: IEC 61010-1:2010 (3rd Edition), UL 61010-1, 3rd Edition, CAN/CSA C22.2 No. 61010-1-12, 3rd Edition, Additional Standards: UL 50E