PAX2 Field-Installable FlexCard Module

Brand: Red Lion Controls

Red Lion’s FlexCard Modules quickly expand the functionality of PAX2C PID controllers to meet application requirements. 

Red Lion’s PAX2C PID controllers offer the capability to add and change FieldCard modules and PAX option cards as your application and communications requirements change. 

Red Lion’s field-upgradeable solutions are the perfect alternative to competitive meters that require a new meter every time conditions change.
Features
  • Field-Installable FlexCard Modules
    • Allows PAX2C PID controllers to quickly meet any PID control application requirement
    • Reduces inventory requirements and expands available PID control monitoring
  • Plug-and-Play Installation
    • FlexCard modules can be installed in any available card slot
  • Variety of FlexCard Module Options
    • Heater current module provides warning and alarm before heater elements fail
    • Integrate multi-zone PID control into a single PAX2C display reducing space and complexity
    • Remote setpoint module offers secondary process inputs or remote setpoint input
  • Easily Programmed
    • Easily configured using Crimson software or keypad on face of meter
    • Simple and intuitive programming

Specifications

Accuracy

  • ± 2 % of Full Scale, 5 to 100 % of Range - PX2FCA10
  • 0.1 % of Span at 0° to 50° C (32° to 122° F) - PX2FCA00

Applications

  • Factory Automation
  • Flow & Temperature
  • Manufacturing Processes
  • Process Control

Approvals & Certifications

  • CE

Control Functions Characteristics

  • PID Control

Delay Time

  • Output on Time Delay for Break Alarm: 1 second - PX2FCA10

Electrical Connectors

  • Rear Terminal: 26 to 16 AWG (0.14 to 1.5 mm²), 0.31” (8 mm) Wire Strip Length
  • Rear Terminal: High Compression Cage-Clamp Terminal Block
  • Top Terminal: 26 to 16 AWG (0.2 to 1.5 mm²), 0.27” (7.0 mm) Wire Strip Length
  • Top Terminal: Spring Cage Terminal Block

Frequency

  • 50/400 Hz - PX2FCA10

Input

  • 0-10 Vdc - PX2FCA00
  • 0-20 mA DC - PX2FCA00
  • 100 mA AC Output from Current Transformer - PX2FCA10
  • 150 mA - Max.
  • 30 V, Max.

Input Impedance

  • 10 ohms - PX2FCA00
  • 538 kiloohms - PX2FCA00

Load

  • Overload: 200 mA (Continuous) - PX2FCA10

Output

  • Current Rating: 1 A DC, Max.
  • Off State Leakage Current: 0.5 μA, Max.
  • VDS On: < 0.2 V at 1 A
  • VDS, Max.

Power Supply

  • Output Power Supply: 18-25 Vdc at 40 mA - Max.

Resistance

  • 5 ohms - PX2FCA10

Torque

  • Rear Terminal: 4.4 to 5.3 In/Lbs (0.5 to 0.6 Nm)

show more