Display
- 5 Digit, 0.56” (14.2 mm) intensity Adjustable Red LED (-19999 to 99999)
Power Requirements
- AC POWER: 50 to 250 Vac 50/60 Hz, 12 VA Isolation: 2300 Vrms for 1 min. to all Inputs and outputs
- DC POWER: 21.6 to 250 Vdc, 6 W DC Out: +24 Vdc @ 100 mA if Input Voltage is greater than 50 Vac/ Vdc +24 Vdc @ 50 mA if Input Voltage is less than 50 Vdc
Input Ranges
- Jumper Selectable
- D.C. Voltages: 200 mV, 2 V, 20 V, 200 V, 10 V
- D.C. Currents: 200 µA, 2 mA, 20 mA, 200 mA
- D.C. Process: 4-20 mA, 1 to 5 Vdc, 0/1 to 10 Vdc
Overrange / Underrange Indication
- Input Overrange Indication: “OLOL”.
- Input Underrange Indication: “ULUL”.
- Display Overrange/Underrange Indication: “.....”/“-.....”
Update Rates
- A/D conversion rate: 20 Readings/sec
- Display update: 500 msec min.
User Inputs
- User Input: Software selectable pull-Up (24.7 KΩ) or pull-down resistor (20 KΩ) that determines active high or active Low Input logic.
- Trigger levels: VIL = 1.0 V max, VIH = 2.4 V min, VMAX = 28 Vdc
- Response Time: 5 msec Typical, 100 msec debounce (Activation and release)
Memory
- Nonvolatile E2PROM Retains all Programming Parameters when Power is removed
Output
- Response Time: Turn on Time: 4 msec Max. Turn Off Time: 4 msec max
- Life Expectancy: 100,000 minimum Operations
- Isolation to Sensor & User Input Commons: 1400 Vrms for 1 min. Working Voltage: 150 Vrms
- Type: Dual FORM-C Relay
- Contact Rating: 5 Amps @ 120/240 Vac or 28 Vdc (Resistive load), 1/8 H.P. @ 120 Vac (Inductive load)
Environmental Conditions
- Operating Temperature: 0 to 50° C
- Storage Temperature: -40 to 70° C
- Operating and storage humidity: 0 to 85 % Max. Relative Humidity (Non-Condensing)
- Vibration to IEC 68-2-6: Operational 5 to 150 Hz, 2 g
- Shock to IEC 68-2-27: Operational 30 g (10 g Relay).
- Altitude: Up to 2,000 metres
Connections
- High Compression Cage-Clamp Terminal Block
- Wire Strip Length: 0.3” (7.5 mm)
- Wire Gage: 30-14 AWG Copper wire
- Torque: 4.5 inch-lbs (0.51 N-m) Max.
Construction
- This unit is rated for NEMA 4X/IP65 outdoor use. IP20 Touch safe. Installation Category II, Pollution Degree 2. One piece bezel/case. Flame resistant. Synthetic Rubber keypad. Panel gasket and Mounting clip included.
Certifications & Approvals
- CE Approved EN 61326-1 Immunity to Industrial Locations Emission CISPR 11 Class A
- Safety Requirements for Electrical Equipment for measurement, Control, and Laboratory use: EN 61010-1: General Requirements
- RoHS Compliant
- UL Listed: File #E179259 for Model No. PAXLA0U0 Only
- Type 4X Enclosure Rating (Face Only)
- IP65 Enclosure Rating (Face Only)
- IP20 Enclosure Rating (Rear of unit)