PAX Lite Panel Meter Series

Brand: Red Lion Controls

The PAXLA is a versatile meter available as a DC volt, current, or process meter with scaling and dual Form C relay outputs. The meter is programmed through the front panel buttons and the use of jumpers. The RST button can also function as a front panel display reset.

Once the front panel programming is complete, the buttons can be disabled by a user input setting. The meter has been specifically designed for harsh industrial environments. With a NEMA 4X/IP65 sealed bezel and extensive testing to meet CE requirements, the meter provides a tough yet reliable application solution.

SAFETY SUMMARY
All safety regulations, local codes and instructions that appear in this and corresponding literature, or on equipment, must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. 

If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

Specifications

Display

  • 5 Digit, 0.56” (14.2 mm) intensity Adjustable Red LED (-19999 to 99999)

Power Requirements

  • AC POWER: 50 to 250 Vac 50/60 Hz, 12 VA Isolation: 2300 Vrms for 1 min. to all Inputs and outputs
  • DC POWER: 21.6 to 250 Vdc, 6 W DC Out: +24 Vdc @ 100 mA if Input Voltage is greater than 50 Vac/ Vdc +24 Vdc @ 50 mA if Input Voltage is less than 50 Vdc

Input Ranges

  • Jumper Selectable
  • D.C. Voltages: 200 mV, 2 V, 20 V, 200 V, 10 V
  • D.C. Currents: 200 µA, 2 mA, 20 mA, 200 mA
  • D.C. Process: 4-20 mA, 1 to 5 Vdc, 0/1 to 10 Vdc

Overrange / Underrange Indication

  • Input Overrange Indication: “OLOL”.
  • Input Underrange Indication: “ULUL”.
  • Display Overrange/Underrange Indication: “.....”/“-.....”

A/D Converter

  • 16-bit resolution

Update Rates

  • A/D conversion rate: 20 Readings/sec
  • Display update: 500 msec min.

User Inputs

  • User Input: Software selectable pull-Up (24.7 KΩ) or pull-down resistor (20 KΩ) that determines active high or active Low Input logic.
  • Trigger levels: VIL = 1.0 V max, VIH = 2.4 V min, VMAX = 28 Vdc
  • Response Time: 5 msec Typical, 100 msec debounce (Activation and release)

Memory

  • Nonvolatile E2PROM Retains all Programming Parameters when Power is removed

Output

  • Response Time: Turn on Time: 4 msec Max. Turn Off Time: 4 msec max
  • Life Expectancy: 100,000 minimum Operations
  • Isolation to Sensor & User Input Commons: 1400 Vrms for 1 min. Working Voltage: 150 Vrms
  • Type: Dual FORM-C Relay
  • Contact Rating: 5 Amps @ 120/240 Vac or 28 Vdc (Resistive load), 1/8 H.P. @ 120 Vac (Inductive load)

Environmental Conditions

  • Operating Temperature: 0 to 50° C
  • Storage Temperature: -40 to 70° C
  • Operating and storage humidity: 0 to 85 % Max. Relative Humidity (Non-Condensing)
  • Vibration to IEC 68-2-6: Operational 5 to 150 Hz, 2 g
  • Shock to IEC 68-2-27: Operational 30 g (10 g Relay).
  • Altitude: Up to 2,000 metres

Connections

  • High Compression Cage-Clamp Terminal Block
  • Wire Strip Length: 0.3” (7.5 mm)
  • Wire Gage: 30-14 AWG Copper wire
  • Torque: 4.5 inch-lbs (0.51 N-m) Max.

Construction

  • This unit is rated for NEMA 4X/IP65 outdoor use. IP20 Touch safe. Installation Category II, Pollution Degree 2. One piece bezel/case. Flame resistant. Synthetic Rubber keypad. Panel gasket and Mounting clip included.

Certifications & Approvals

  • CE Approved EN 61326-1 Immunity to Industrial Locations Emission CISPR 11 Class A
  • Safety Requirements for Electrical Equipment for measurement, Control, and Laboratory use: EN 61010-1: General Requirements
  • RoHS Compliant
  • UL Listed: File #E179259 for Model No. PAXLA0U0 Only
  • Type 4X Enclosure Rating (Face Only)
  • IP65 Enclosure Rating (Face Only)
  • IP20 Enclosure Rating (Rear of unit)

Weight

  • 10.4 oz. (295 g)
show more