KVD Receiver Pressure Regulator

Brand: Danfoss

KVD is a modulating receiver pressure regulator. It opens on falling receiver pressure and bypasses hot gas to maintain the receiver pressure at the regulator setting (adjustable).

KVD and KVR form a regulating system, used to maintain constant and adequately high condensing and receiver pressure in systems with heat-recovery, and in refrigeration and air conditioning systems with air-cooled condensers.
Features
  • Accurate, adjustable pressure regulation
  • Wide operating range
  • Pulsation damping design
  • Stainless steel bellows
  • Compact angle design for easy installation in any position
  • "Hermetic" brazed construction
  • 1/4" access Valve for pressure testing
  • Available with flare and ODF solder connections
  • Compliant with ATEX hazard zone 2

Specifications

Brand

Applications

  • Air Conditioning Systems
  • Air-Cooled Condensers
  • Heat Recovery Systems
  • Refrigeration Equipment

Approvals & Certifications

  • ATEX Hazard Zone 2
  • UL (US) Listed, File SA7200

Electrical Connectors

  • Protective Cap
  • Soldering Connection

Materials of Construction

  • Stainless Steel Bellows

Mounting Position

  • Any Orientation

Operating Pressure

  • Maximum

Pressure Range

  • Factory Setting psig: 145 (kPa: 1,000, bar: 10)
  • Regulating Range psig: 44 to 290 (kPa: 303.4 to 1,999, bar: 3.03 to 19.99)

Process Temperature

  • -45° to 130° C (-49° to 266° F)

Proof Pressure

  • Maximum

Tube Connection

  • 1/2” Tube
  • 5/8” Tube

  • Air conditioning systems
  • Air-cooled condensers
  • Heat recovery systems
  • Refrigeration equipment

show more