SonoSelect 10 Energy Meter
Brand: DanfossThe Danfoss SonoSelect 10 are ultrasonic compact energy meters intended for measuring energy consumption in heating applications for billing purposes.
The meters are designed for remote meter read-out (AMR).
The energy meters consist of an ultrasonic flow sensor, a pair of Pt1000 temperature sensors and a calculator with integrated circuits for temperature measurement, flow calculation and energy calculation.
Features- Proven ultrasonic measuring principle designed for long operating life time
- No calming section or inlet/outlet restrictions
- Low pressure drop down to 0.03 bar at qp
- Compact design
- Extensive change and error log
- Memory: 2 years of data, yearly and monthly values stored (Including pulse input)
- Upgradable with communication modules
- Battery is replacable
- SonoApp usable for Android (Bluetooth LE via dongle)
Specifications
Brand
Accuracy
- Temperature Sensor: Class B Per EN 60751
Ambient Temperature Range
- -25° to 60° C (-13° to 140° F)
Applications
- Heating
- Reverse Flow Indication
Approvals & Certifications
- Data Protocol & Wired M-Bus According to EN 13757-3
- EN 1434 Class 2
Approvals & Certifications
- CPA According to JJG225 -2010
- EMC: Class E1
- MID (DK-0200-MI004-034)
Battery Life
- 16 + 1-Years
BSP Connection
- G 1” A Female
- G 1-1/4” A Female
- G 3/4” A Female
Cable Length
- 5 feet (1.5 metres)
Cable Material
- Polyurethane
Communication
- Baud Rate: 300, 1,200, 2,400, or 9,600 Selectable
- Bluetooth LE Via Dongle
- Integrated M-Bus
- Wireless OMS 868.95 MHz
Display
- 85 x 35 mm 8-Digit LCD Display
Environmental Protection
- IP65
Flow Rate
- 0.6 to 3.5 m³/hour
Humidity
- < 95 %
Input Signal
- 2 Pulse Inputs
Length
- Meter Size (Min.): 4.33” (110 mm)
- Meter Size, Max.
- Temperature Sensor: 1.02” (26 mm)
Materials of Construction
- Temperature Sensor Nipple: Brass, with Pin Lock
Media
- Water Quality with PH 7 to 9.5
Mounting Position
- Flow Sensor: Any (No Inlet or Outlet Restrictions)
Operating Temperature
- Class A: 5° to 55° C (41° to 131° F)
Power Requirement
- 3.6 Vdc Lithium Battery (1 or 2 AA Cells)
Pressure Drop
- psi: 0.435 to 2.321 (kPa: 3 to 16, Mbar: 30 to 160) at Qp 50° C (122° F)
Pressure Range
- Flow Sensor: psi: 232 (kPa: 1,600, bar: 16)
- Temperature Sensor: psi: 363 (kPa: 2,500, bar: 25)
Process Temperature
- 5° to 95° C (41° to 203° F)
Response Time
- 0.5 second - Flow & Energy
- 4 seconds - Temperature
Sensor / Probe Diameter
- Temperature Sensor Size: 0.2” (5.2 mm)
Sensor, Probe Type
- Pt1000 Direct Short, 2-Wire
Storage Temperature
- -25° to 60° C (-13° to 140° F)
Temperature Range
- 0° to 105° C (32° to 221° F)
- Reverse Flow Indication
- Heating