AMV 85/86 Three Point Control Actuator

Brand: Danfoss

The actuators AMV 85 and AMV 86 are used with VFM 2 (DN 150-250), VFS 2 (DN 65-100), VF2/3 (DN 125, 150) and AFQM (DN150-250) valves.
Features
  • "Self stroking" function
  • Load related "switch off" function that prevents overloading
  • Manual operation
  • Diagnostic LED

Specifications

Brand

Ambient Temperature

  • 0° to 55° C (32° to 131° F)

Approvals & Certifications

  • CE
  • EMC Directive 89/336/EEC, 92/31/EEC, 93/68/EEC, EN 50081-1 & EN 50082-1
  • Low Voltage Directive (LVD) 73/23/EEC & 93/68/EEC, EN 60730/2/14

Class

  • Protection Class I (230 V)
  • Protection Class III (24 V)

Consumption

  • 10.5 VA - Power Consumption (AMV 85)
  • 23 VA - Power Consumption (AMV 86)

Electrical Connectors

  • Cable Gland
  • Two M16 x 1.5

Environmental Protection

  • IP54

Frequency

  • 50/60 Hz

Function

  • Self Stroking
  • Switch Off (Prevents Overloading)

Indication

  • Diagnostic LED

Input Signal

  • Control Input Signal: 3-Point

Mounting Position

  • Horizontal
  • Upright

Operation

  • Manual Operation

Override

  • Manual Override

Power Supply

  • 230 Vac, 10 to -15 %
  • 24 Vac, 10 to -15 %

Process Temperature

  • Maximum

Speed

  • 3 sec/mm - Model AMV 86
  • 8 sec/mm - Model AMV 85

Storage Temperature

  • -40° to 70° C (-40° to 158° F)

show more